Electric drive technology

By continuing to use this site you consent to the use of cookies on your device as described in our Cookie Policy unless you have disabled them. You can change your Cookie Settings at any time but parts of our site will not function correctly without them.


VF-nC3 Nanodrive

The compact class

 

VF-nC3 Nanodrive

The VF-nC3 excels at its compactness, simple installation and easy start-up. Settings are easily done with the convenient jog dial.
Its sensorless vector control ensures an excellent efficiency of your drive and makes it suitable also for dynamic applications. The tolerance of the reaction time to external signals is constant and as low as ±1 ms – the VF-nC3 controls the drive with high efficiency and repeat accuracy.
Due to its integrated high attenuation EMC filters it can be operated in any environment.

  • Extremely compact
  • EMC filter C1
  • Easy configuration
  • PID control, logic functions AND, OR
  • RS485 interface
  • Quick stop
Standard specifications VF-nC3
VFnC3S 1-ph. 120 V
Applicable motor [kW] 0,1 ….. 0,75 kW
Output current [A] 0,7 ….. 4,2 A
Power supply 1-ph. 100 V ... 120 V, 50/60 Hz
VFnC3S 1-ph.240 V
Applicable motor [kW] 0,1 ….. 2,2 kW
Output current [A] 0,7 ….. 10,0 A
Power supply 1-ph. 200 V ... 240 V, 50/60 Hz
VFnC3 3-ph.240 V
Applicable motor [kW] 0,1 ….. 4,0 kW
Output current [A] 0,7 ….. 16,7 A
Power supply 1-ph. 200 V ... 240 V, 50/60 Hz
Capacity [kVA] at 220V 0,3 ….. 6,7 kVA
Rated output voltage 120 V - class 3-ph. 50-240 V (maximum output voltage is 2 times input source voltage)
240 V - class 1-ph. & 3-ph. 50-240 V (maximum output voltage is same as input source voltage)
Output frequency range 0,1-400 Hz
Overload capability 150 % of output current for 60 s, 200 % for 0,5 s
Maximun fluctuation Voltage: ± 10 % under full load, Frequency ± 5 %
Ambient level max. 3000 m AMSL
Vibrations < 5,9 m/s² (10…55 Hz)
Ambient temperature -10 to +60°C
Relative humidity 5 to 95 % (condensation-free)
Protection class IP20
Cooling method 120 V-class to 0,4 kW self-cooling without fan, from 0,75 kW self-cooling with integrated fan, 240 V-class to 0,75 kW self-cooling without fan, from 1,5 kW self-cooling with integrated fan
EMC filter 1-ph. 120 V External (option); 1-ph. 240 V Integrated IEC61800-3 C1 to 5 m motor line, IEC61800-3 C2 to 10 m motor line; 3-ph. 240 V External (option)

Downloads

VF-nC3_Flyer_neutral_e VF-nC3_Flyer_neutral_e
VF-nC3_Detailed Manual_neutral_e_e6581595 VF-nC3_Detailed Manual_neutral_e_e6581595
FI-Overview_Flyer_neutral_e_16a83010 FI-Overview_Flyer_neutral_e_16a83010